Accessories catalog
Input/Output Module
EA_IntBoard_IOM-03Description
The RC5 can be supplied with an IOM on request to provide control and indication functions. IOM has 12 galvanically isolated digital inputs and 12 digital outputs with normally open and normally closed contacts.
Characteristic
Main | |
---|---|
Digital inputs: | |
Rated voltages of signal applied to digital inputs | 110/125/220 V DC |
Pickup voltage of signal applied to digital inputs | Above 100 V |
Reset voltage | Below 30 V |
Maximum continuous voltage of signal applied to digital inputs | 275 V |
Input resistance | 125 kOhm |
Digital outputs: | |
Rated voltage | 250 V AC |
Rated current | 16 A |
Breaking capacity DC1 (at L/R=1ms): 30/110/220 V | 16/0.3/0.12 A |
Minimum switching load | 500 mW (10V/5mA) |
Applicable product | Rec15_AI1_5p, Rec25_AI1_5p |